Section 296-96-14020. What construction requirements apply to hoistway landings and entrances?  


Latest version.
  • (1) Every hoistway landing must be protected on all sides other than the landing opening side with a standard guard rail and intermediate guard rail. All landing except the bottom landing must have a toe board installed on all sides except the landing opening side.
    (2) All hoistway entrances must be not less than 6 feet 6 inches in height and in no case may the width exceed the corresponding car dimensions.
    (3) All hoistway entrances must be provided with an approved maze or with a hoistway gate which must:
    (a) Be at least 36 inches in height;
    (b) Extend downward to within one inch of the landing sill;
    (c) Be of the self-closing type, designed to swing horizontally out from the hoistway and closing against a full jam stop;
    (d) Be located within 4 inches of the edge of the landing sill;
    (e) Have a "DANGER" sign conspicuously posted on the landing side of the hoistway gate; and
    (f) Withstand a 250 pound horizontal thrust.
    (4) On new installations, all projections extending inwardly from a hoistway enclosure at the entrance side of the car platform must be beveled and guarded on their underside by a smooth solid material set at an angle of not less than 60 degrees nor more than 75 degrees from the horizontal when cars are not equipped with gates.
    [Statutory Authority: RCW 70.87.020, 70.87.030, 70.87.034, 70.87.120, 70.87.185 and chapter 70.87 RCW. WSR 01-02-026, § 296-96-14020, filed 12/22/00, effective 1/22/01.]