Washington Administrative Code (Last Updated: November 23, 2016) |
Title 51. Enterprise Services, Department of (Building Code Council) |
Chapter 51-51. State Building Code adoption and amendment of the 2015 edition of the International Residential Code. |
Section 51-51-0507. Section R507—Decks.
Latest version.
- R507.2.4 Deck lateral load connections. The lateral load connection required by Section R507.1 shall be permitted to be in accordance with Figure R507.2.3(1) or R507.2.3(2). Where the lateral load connection is provided in accordance with Figure R507.2.3(1), hold-down tension devices shall be installed in not less than two locations per deck, within 24 inches of each end of the deck. Each device shall have an allowable stress design capacity of not less than 1500 pounds (6672 N). Where the lateral load connections are provided in accordance with Figure R507.2.3(2), the hold-down tension devices shall be installed in not less than four locations per deck, and each device shall have an allowable stress design capacity of not less than 750 pounds (3336 N).EXCEPTION:Decks not more than 30 inches above grade at any point may be unattached.Table R507.2.1Placement of Lag Screws and Bolts in Deck Ledgers and Band JoistsFor SI:1 inch = 25.4 mm.aLag screws or bolts shall be staggered from the top to the bottom along the horizontal run of the deck ledger in accordance with Figure R507.2.1(1).bMaximum 5 inches.cFor engineered rim joists, the manufacturer's recommendations shall govern.dThe minimum distance from bottom row of lag screws to the top edge of the ledger shall be in accordance with Figure R507.2.1(1).eThe 2 inches may be reduced to 3/4 inch when the band joist is directly supported by a mudsill, a header or by double top wall plates.