Section 51-50-1006. Section 1006—Number of exits and exit access doorways.
Latest version.
- 1006.2.2.6 Electrical equipment rooms. Rooms containing electrical equipment shall be provided with a second exit or exit access doorways as required by NFPA 70 Article 110 where all of the following apply:1. The electrical equipment is rated at 1,200 amperes or more.2. The electrical equipment is over 6 feet (1829 mm) wide.3. The electrical equipment contains overcurrent devices, switching devices or control devices.