Section 51-50-1006. Section 1006—Number of exits and exit access doorways.  


Latest version.
  • 1006.2.2.6 Electrical equipment rooms. Rooms containing electrical equipment shall be provided with a second exit or exit access doorways as required by NFPA 70 Article 110 where all of the following apply:
    1. The electrical equipment is rated at 1,200 amperes or more.
    2. The electrical equipment is over 6 feet (1829 mm) wide.
    3. The electrical equipment contains overcurrent devices, switching devices or control devices.
    [Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 16-03-064, § 51-50-1006, filed 1/19/16, effective 7/1/16.]