Section 51-50-1004. Section 1004.  


Latest version.
  • 1004.2 Increased occupant load. The occupant load permitted in any building, or portion thereof, is permitted to be increased from that number established for the occupancies in Table 1004.1.2, provided that all other requirements of the code are also met based on such modified number and the occupant load does not exceed one occupant per 7 square feet (0.65 m2) of occupiable floor space. Where required by the building official, an approved aisle, seating or fixed equipment diagram substantiating any increase in occupant load shall be submitted. Where required by the building official, such diagram shall be posted. See WAC 170-295-0080 (1)(b) for day care licensed by the state of Washington.
    [Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 16-03-064, § 51-50-1004, filed 1/19/16, effective 7/1/16.]
RCW 19.27.031 and 19.27.074. WSR 16-03-064, § 51-50-1004, filed 1/19/16, effective 7/1/16.