  • C406.7 Reduced energy use in service water heating. Buildings shall comply with Sections C406.7.1 and C406.7.2.
    C406.7.1 Building type. Not less than 90 percent of the conditioned floor area shall be of the following types:
    1. Group R-1: Boarding houses, hotels or motels.
    2. Group I-2: Hospitals, psychiatric hospitals and nursing homes.
    3. Group A-2: Restaurants and banquet halls or buildings containing food preparation areas.
    4. Group F: Laundries.
    5. Group R-2: Buildings with residential occupancies.
    6. Group A-3: Health clubs and spas.
    7. Buildings with a service hot water load of 10 percent or more of total building energy loads, as shown with an energy analysis as described in Section C407.
    C406.7.2 Load fraction. Not less than 60 percent of the annual building service hot water energy use, or not less than 100 percent of the annual building service hot water heating energy use in buildings subject to the requirements of Section C403.5.4, shall be provided by one or more of the following:
    1. Service hot water system delivering heating requirements using heat pump technology with a minimum COP of 3.0.
    2. Waste heat recovery from service hot water, heat recovery chillers, building equipment, process equipment, a combined heat and power system, or other approved system.
    3. Solar water-heating systems.