Section 51-11C-405027. Section C405.2.7—Exterior lighting controls.  


Latest version.
  • C405.2.7 Exterior lighting controls. Lighting for exterior applications other than emergency lighting that is intended to be automatically off during building operation, lighting specifically required to meet health and life safety requirements or decorative gas lighting systems shall:
    1. Be provided with a control that automatically turns off the lighting as a function of available daylight.
    2. Where lighting the building façade or landscape, the lighting shall have controls that automatically shut off the lighting as a function of dawn/dusk and a set opening and closing time.
    3. Where not covered in Item 2, the lighting shall have controls configured to automatically reduce the connected lighting power by at least 30 percent from no later than 12 midnight to 6 a.m. or from one hour after business closing to one hour before business opening or during any period when no activity has been detected for a time of no longer than 15 minutes.
    Time switches shall be capable of retaining programming and the time setting for at least 10 hours without power.
    EXCEPTION:
    Lighting for covered vehicle entrances or exits from buildings or parking structures where required for safety, security or eye adaption.
    [Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. WSR 16-03-072, § 51-11C-405027, filed 1/19/16, effective 7/1/16.]