Section 51-11C-403239. Table C403.2.3(9) and Table C403.2.3(10)—Minimum efficiency requirements.  


Latest version.
  • Table C403.2.3(9)
    Minimum Efficiency RequirementsAir Conditioners and Condensing Units Serving Computer Rooms
    a
    Net sensible cooling capacity: The total gross cooling capacity less the latent cooling less the energy to the air movement system. (Total Gross – Latent – Fan Power.)
    b
    Sensible coefficient of performance (SCOP-127): A ratio calculated by dividing the net sensible cooling capacity in watts by the total power input in watts (excluding reheaters and humidifiers) at conditions defined in ASHRAE Standard 127. The net sensible cooling capacity is the gross sensible capacity minus the energy dissipated into the cooled space by the fan system.
    Table C403.2.3(10)
    Minimum Efficiency RequirementsHeat Transfer Equipment
     
    NR = No requirement.
    a
    Chapter 6 of the referenced standard contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.