Washington Administrative Code (Last Updated: November 23, 2016) |
Title 51. Enterprise Services, Department of (Building Code Council) |
Chapter 51-11C. State Building Code adoption and amendment of the 2015 edition of the International Energy Conservation Code, Commercial. |
Section 51-11C-403232. Table C403.2.3(2)—Minimum efficiency requirements—Electrically operated unitary and applied heat pumps.
Latest version.
- Table C403.2.3(2)Minimum Efficiency Requirements—Electrically Operated Unitary and Applied Heat PumpsFor SI:1 British thermal unit per hour = 0.2931 W, °C = [(°F) - 32]/1.8.aChapter 6 of the referenced standard contains a complete specification of the referenced test procedure, including the reference year version of the test procedure.bSingle-phase, air-cooled air conditioners less than 65,000 Btu/h are regulated by NAECA. SEER values are those set by NAECA.[Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. WSR 16-03-072, § 51-11C-403232, filed 1/19/16, effective 7/1/16. Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11-403232 (codified as WAC 51-11C-403232), filed 2/1/13, effective 7/1/13.]Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency.
RCW 19.27A.025, 19.27A.160, and 19.27.074. WSR 16-03-072, § 51-11C-403232, filed 1/19/16, effective 7/1/16. Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11-403232 (codified as WAC 51-11C-403232), filed 2/1/13, effective 7/1/13.