Section 51-11C-40248. Section C402.5.8—Recessed lighting.  


Latest version.
  • C402.5.8 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be all of the following:
    1. IC rated.
    2. Labeled as having an air leakage rate of not more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E 283 at a 1.57 psf (75 Pa) pressure differential.
    3. Sealed with a gasket or caulk between the housing and interior wall or ceiling covering.
    [Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. WSR 16-03-072, § 51-11C-40248, filed 1/19/16, effective 7/1/16. Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11C-40248, filed 2/1/13, effective 7/1/13.]