Section 388-97-3280. Safety—Handrails.  


Latest version.
  • The nursing home must:
    (1) Provide handrails on each side of all corridors and stairwells accessible to residents; and
    (2) In new construction ensure that:
    (a) Ends of handrails are returned to the walls;
    (b) Handrails are mounted thirty to thirty-four inches above the floor and project not more than three and three-quarters inches from the wall; and
    (c) Handrails terminate not more than six inches from a door.
    [Statutory Authority: Chapters 18.51 and 74.42 RCW and 42 C.F.R. 489.52. WSR 08-20-062, § 388-97-3280, filed 9/24/08, effective 11/1/08.]