Section 388-107-0950. Safety—Handrails.  


Latest version.
  • The facility must:
    (1) Provide handrails on each side of all corridors and stairwells accessible to residents and ensure that:
    (a) Ends of handrails are returned to the walls;
    (b) Handrails are mounted thirty to thirty-four inches above the floor; and
    (c) Handrails terminate not more than six inches from a door.
    (2) Equip stairways with more than one riser and ramps with slopes greater than one in twenty with handrails on both sides. Ensure that ends of handrails are designed in a manner that eliminates a hooking hazard.
    (3) Must maintain nonskid surfaces on all stairways and ramps used by residents.
    [Statutory Authority: Chapter 70.97 RCW. WSR 14-19-071, § 388-107-0950, filed 9/12/14, effective 10/13/14.]