Section 296-96-23332. What requirements apply to anti-creep leveling devices?  


Latest version.
  • Each elevator must be provided with an anticreep leveling device conforming to the following specifications:
    (1) It must maintain the car within 3 inches of the landing regardless of the position of the hoistway door.
    (2) For electrohydraulic elevators, it must operate the car only in the up direction.
    (3) For maintained pressure hydraulic elevators, it must operate the car in both directions.
    (4) Its operation may depend on the availability of the electric power supply provided that:
    (a) The power supply line disconnecting means required by WAC 296-96-23274 is kept in the closed position at all times except during maintenance, repairs, and inspections;
    (b) The electrical protective devices required by WAC 296-96-23334 must not cause the power to be removed from the device.
    [Statutory Authority: RCW 70.87.020, 70.87.030, 70.87.034, 70.87.120, 70.87.185 and chapter 70.87 RCW. WSR 01-02-026, § 296-96-23332, filed 12/22/00, effective 1/22/01.]
RCW 70.87.020, 70.87.030, 70.87.034, 70.87.120, 70.87.185 and chapter 70.87 RCW. WSR 01-02-026, § 296-96-23332, filed 12/22/00, effective 1/22/01.

Rules

296-96-23274,296-96-23334,