Section 296-96-23207. What requirements apply to platform guards (aprons)?  


Latest version.
  • The entrance side of the platform of passenger and freight elevators equipped with leveling devices or truck-zoning devices must have smooth metal guard plates of not less than 0.0598 inch thick steel, or material of equivalent strength and stiffness, adequately reinforced and braced to the car platform and conforming to the following:
    (1) The guard plate must extend no less than the full width of the widest hoistway door opening.
    (2) It must have a straight vertical face, extending below the floor surface of the platform, of no less than the depth of the leveling of truck zone, plus 3 inches.
    (3) If new guards are installed, the lower portion of the guard must be bent back at an angle of not less than 60 degrees nor more than 75 degrees from the horizontal.
    (4) The guard plate must be securely braced and fastened in place to withstand a constant force of not less than 15-lbf applied at right angles to and at any position on its face without permanent deformation.
    [Statutory Authority: RCW 70.87.020, 70.87.030, 70.87.034, 70.87.120, 70.87.185 and chapter 70.87 RCW. WSR 01-02-026, § 296-96-23207, filed 12/22/00, effective 1/22/01.]