Section 296-96-23151. What requirements apply to hoistway door closing devices?
Latest version.
- (1) Horizontally sliding doors on automatic-operation elevators must be equipped with door closers that automatically close an open door if the car for any reason leaves the landing zone.(2) Horizontal swinging single or center-opening doors on automatic-operation elevators must be self-closing.(3) Door closers are not required for the swinging portion of combination horizontally sliding and swinging doors.(4) On center-opening doors that utilize relating cables if the cabling fails or when the cabling is replaced a method shall be provided to ensure that both doors automatically close if the car for any reason leaves the landing zone.[Statutory Authority: RCW 70.87.020, 70.87.030, 70.87.034, 70.87.120, 70.87.185, 70.87.190, 2002 c 98, 2003 c 143 and 2004 c 66. WSR 04-12-047, § 296-96-23151, filed 5/28/04, effective 6/30/04. Statutory Authority: RCW 70.87.020, 70.87.030, 70.87.034, 70.87.120, 70.87.185 and chapter 70.87 RCW. WSR 01-02-026, § 296-96-23151, filed 12/22/00, effective 1/22/01.]
RCW 70.87.020, 70.87.030, 70.87.034, 70.87.120, 70.87.185, 70.87.190, 2002 c 98, 2003 c 143 and 2004 c 66. WSR 04-12-047, § 296-96-23151, filed 5/28/04, effective 6/30/04. Statutory Authority: RCW 70.87.020, 70.87.030, 70.87.034, 70.87.120, 70.87.185 and chapter 70.87 RCW. WSR 01-02-026, § 296-96-23151, filed 12/22/00, effective 1/22/01.