Section 296-96-23133. What requirements apply to counterweight pit guards?  


Latest version.
  • (1) Where feasible, unperforated metal guards must be installed in the pit on the open side or sides on all counterweights where spring or solid-type buffers are used or where oil buffers attached to the counterweights are used. Except, where compensating chairs or ropes are attached to the counterweight the guard may be omitted on the side facing the car to which the chains or ropes are attached.
    (2) Guards must extend from a point no more than 12 inches above the pit floor to a point at least 7 feet but not more than 8 feet above the floor; and be fastened to a properly reinforced and braced metal frame that is at least equal in strength and stiffness to No. 14 U.S. gauge sheet steel.
    [Statutory Authority: RCW 70.87.020, 70.87.030, 70.87.034, 70.87.120, 70.87.185 and chapter 70.87 RCW. WSR 01-02-026, § 296-96-23133, filed 12/22/00, effective 1/22/01.]