Section 296-96-23111. Are guards required for windows in hoistway enclosures?  


Latest version.
  • (1) Guards are required on outside hoistway windows if the windows are located:
    (a) Ten stories or less above a thoroughfare; or
    (b) Three stories or less above the roof of an adjacent building.
    (2) Hoistway windows can be guarded by one of the following methods:
    (a) By vertical bars at least 5/8 inch in diameter or equivalent, spaced no more than 10 inches apart, permanently and securely fastened in place; and
    (b) By metal-sash windows having solid section steel muntins of no less than 1/8 inch thickness, spaced no more than 8 inches apart.
    (3) Exterior hoistway windows must be identified with 4-inch high letters marked "elevator."
    [Statutory Authority: RCW 70.87.020, 70.87.030, 70.87.034, 70.87.120, 70.87.185 and chapter 70.87 RCW. WSR 01-02-026, § 296-96-23111, filed 12/22/00, effective 1/22/01.]