Section 296-96-14060. What requirements apply to hoisting ropes?  


Latest version.
  • (1) Hoisting ropes must be of good grade traction elevator wire rope and must:
    (a) Be not less than 3/8 inch in diameter.
    (b) Provide a safety factor of 5 based on the maximum weight supported.
    (c) Be of sufficient length to prevent the counterweight from striking the overhead structure when car is at the bottom, and prevent the car from striking the overhead before the counterweight is at its lower limit of travel.
    (d) Cable fastenings shall be by babbitted tapered elevator sockets or other acceptable methods approved by the department. If cable clamps are used, a minimum of three cable clamps must be provided. U-shaped clamps shall not be acceptable.
    (e) Where passed around a metal or other object less than three times the diameter of the cable, have a thimble of the correct size inserted in the eye.
    (2) Approved sockets or fittings with the wire properly turned back and babbitted may be used in place of clamps noted in subsection (1)(d) of this section.
    [Statutory Authority: RCW 70.87.020, 70.87.030, 70.87.034, 70.87.120, 70.87.185, 70.87.190, 2002 c 98, 2003 c 143 and 2004 c 66. WSR 04-12-047, § 296-96-14060, filed 5/28/04, effective 6/30/04. Statutory Authority: RCW 70.87.020, 70.87.030, 70.87.034, 70.87.120, 70.87.185 and chapter 70.87 RCW. WSR 01-02-026, § 296-96-14060, filed 12/22/00, effective 1/22/01.]
RCW 70.87.020, 70.87.030, 70.87.034, 70.87.120, 70.87.185, 70.87.190, 2002 c 98, 2003 c 143 and 2004 c 66. WSR 04-12-047, § 296-96-14060, filed 5/28/04, effective 6/30/04. Statutory Authority: RCW 70.87.020, 70.87.030, 70.87.034, 70.87.120, 70.87.185 and chapter 70.87 RCW. WSR 01-02-026, § 296-96-14060, filed 12/22/00, effective 1/22/01.