Washington Administrative Code (Last Updated: November 23, 2016) |
Title 296. Labor and Industries, Department of |
Chapter 296-96. Safety regulations and fees for all elevators, dumbwaiters, escalators and other conveyances. |
Section 296-96-11054. What requirements apply to the location and construction of handholds?
Latest version.
- (1) Handholds attached to the belt must be provided and installed so that they are not less than 4 feet nor more than 4 feet 8 inches above the step tread. These handholds must be available on both the "up" and "down" run of the belt.(2) All handhold grab surfaces must be at least 4 1/2 inches in width. Fastenings must not come within one inch of the belt edge.(3) All handholds must be capable of withstanding, without damage, a 300 pound load applied parallel to the belt run.(4) All handholds must have corresponding steps. When a handhold is removed for any reason, the corresponding step and handhold for the opposite direction of travel must also be removed before the lift resumes operation.