Section 296-96-07220. What are the requirements for traveling cables?  


Latest version.
  • (1) All traveling cables must conform to the National Electrical Code (NEC) in effect at the time of installation or major alteration.
    (2) Where circuits through the traveling cable(s) exceed 30 volts, a means must be provided to stop the power automatically if the traveling cables part.
    [Statutory Authority: RCW 70.87.020, 70.87.030, 70.87.034, 70.87.120, 70.87.185 and chapter 70.87 RCW. WSR 01-02-026, § 296-96-07220, filed 12/22/00, effective 1/22/01.]