Section 296-96-05020. What requirements apply to the construction and fire safety of hoistway enclosures?  


Latest version.
  • Generally, local codes and ordinances govern hoistway enclosure construction. When not in conflict with a local code requirement, the enclosure must:
    (1) Be built to a height of 7 feet above each floor, landing and adjacent stairway tread;
    (2) Extend (adjacent to the counterweights) the full height of the floor and 8 inches beyond the counterweight raceway;
    (3) Be constructed of either solid material or material with openings that will reject a 2-inch diameter ball; and
    (4) Be supported and braced so that it does not deflect more than 1 inch when subjected to a force of 100 pounds applied perpendicular at any point.
    (5) A full height hoistway enclosure is required only on the side(s) of the material lift for which the car is not equipped with a gate or enclosure.
    [Statutory Authority: Chapter 70.87 RCW. WSR 07-24-041, § 296-96-05020, filed 11/30/07, effective 1/1/08. Statutory Authority: RCW 70.87.020, 70.87.030, 70.87.034, 70.87.120, 70.87.185 and chapter 70.87 RCW. WSR 01-02-026, § 296-96-05020, filed 12/22/00, effective 1/22/01.]