  • (1) LULAs may be permitted in churches, private clubs, and buildings listed on the historical register that are not required to comply with accessibility requirements.
    (2) For LULAs installed according to subsection (1) of this section a form provided by the department must be signed by the local building official.
    (3) LULAs must be equipped with an emergency communication device meeting the requirements of WAC 296-96-02330.
    (4) ASME A17.1-5.2.1.7.1 Elevator machine rooms, control rooms, and machinery spaces containing an elevator driving machine not located in the hoistway shall have clear headroom of not less than two thousand one hundred thirty millimeters (eighty-four inches).
    (5) All maintenance, examination, and safety tests must be in accordance with ASME A17.1-8.6 and WAC 296-96-23605(3).
    [Statutory Authority: Chapter 70.87 RCW. WSR 13-24-066, § 296-96-02595, filed 11/27/13, effective 1/1/14; WSR 07-24-041, § 296-96-02595, filed 11/30/07, effective 1/1/08.]
Chapter 70.87 RCW. WSR 13-24-066, § 296-96-02595, filed 11/27/13, effective 1/1/14; WSR 07-24-041, § 296-96-02595, filed 11/30/07, effective 1/1/08.