Washington Administrative Code (Last Updated: November 23, 2016) |
Title 296. Labor and Industries, Department of |
Chapter 296-835. Dipping and coating operations (dip tanks). |
Section 296-835-12025. Provide additional fire protection for large dip tanks.
Latest version.
- You must:• Provide at least one automatic fire extinguishing system or an automatic dip tank cover if the tank:– Holds one hundred fifty gallons or more of liquidOR– Has four square feet or more of liquid surface area.• Make sure automatic fire extinguishing systems or automatic dip tank covers meet the requirements of Table 1.Exemption: An automatic fire extinguishing system or an automatic dip tank cover is not required for a hardening or tempering tank that:• Holds less than five hundred gallonsOR• Has less than twenty-five square feet of liquid surface area.Table 1: Automatic Fire Protection System RequirementsReference: Automatic fire extinguishing systems have specific requirements. See:– WAC 296-24-622 for automatic dry chemical extinguishing system requirements– WAC 296-24-623 for automatic carbon dioxide extinguishing system requirements– WAC 296-24-627 for automatic water spray extinguishing system and automatic foam extinguishing system requirements.
Rules
296-24-622,296-24-623,296-24-627,