Section 296-826-40050. Other refrigerated storage equipment.  


Latest version.
  • (1) You must discharge ammonia to storage by using either:
    (a) A receiver with an automatic float valve; or
    (b) A high pressure liquid drain trap of suitable capacity.
    (2) You must make sure receivers are:
    (a) Designed for at least 250 psig; and
    (b) Equipped with all of the following:
    (i) Necessary connections;
    (ii) Safety relief valves;
    (iii) Gauging devices.
    (3) You must cover insulated containers and pipelines with material that meets all of the following:
    (a) Thick enough for the temperatures it will be exposed to;
    (b) Supported;
    (c) Weather and fire resistant.