(1) You must provide a minimum distance of five feet between aboveground and underground containers that have more than a twelve hundred gallon capacity each.
(2) You must protect containers from floating away, in areas with a potential for high flood waters, by providing either:
(a) Secure anchorage; or
(b) Adequate pier height.
(3) You must follow Table 2 for aboveground, nonrefrigerated containers.