Washington Administrative Code (Last Updated: November 23, 2016) |
Title 296. Labor and Industries, Department of |
Chapter 296-811. Fire brigades. |
Section 296-811-40015. Self-contained breathing apparatus' (SCBAs).
Latest version.
- • Provide SCBAs, other than escape self-contained breathing apparatus' (ESCBAs), and make sure they are used by each fire brigade member who does interior structural firefighting.• Make sure SCBAs do the following:– Meet the requirements found in chapter 296-842 WAC, Respirators.– Are positive-pressure or pressure-demand type.– Use only compressed-air cylinders that:■ Meet department of transportation (DOT) and the National Institute for Occupational Safety and Health (NIOSH) requirements.– Have a service life of at least thirty minutes, as required by 42 C.F.R., Part 84.– Have an automatic alarm that can be heard when seventy-five to eighty percent of its service life has been used up.Note:• An SCBA can have a quick-disconnect valve or "buddy breathing" accessory only if the valve or accessory does not do any of the following:– Damage the SCBA.– Restrict the SCBA's air flow.– Interfere with the SCBA's normal operation.– The "buddy breathing" accessory or quick-disconnect valve need not be certified by NIOSH.
Rules