Section 296-800-28045. Make sure electrical equipment has overcurrent protection.  


Latest version.
  • You must:
    • Make sure all electrical circuits that are rated at 600 volts or less have overcurrent protection.
    • Protect conductors and equipment from overcurrent according to their ability to safely conduct electrical current.
    • Make sure overcurrent devices do not interrupt the continuity of grounded conductors unless all conductors are opened at the same time, except for motor running overload protection.
    – Locate or shield fuses and circuit breakers so that employees will not be burned or otherwise injured by their operation.
    – Make sure handles or levers of circuit breakers, and similar parts that may move suddenly in such a way that persons in the vicinity are likely to be injured by being struck by them, are guarded or isolated.
    • Make sure the following fuses and thermo cutouts have disconnecting means:
    – All cartridge fuses accessible to nonqualified persons.
    – All fuses in circuits over 150 volts to ground.
    – All thermal cutouts on circuits over 150 volts to ground.
    • The disconnecting means must be installed so you can disconnect the fuses or thermal cutouts without disrupting service to equipment and circuits unrelated to those protected by the overcurrent device.
    • Provide easy access to overcurrent devices for each employee or authorized building management personnel.
    • Locate overcurrent devices:
    – Away from easily ignitable material.
    – Where they are not exposed to physical damage.
    • Make sure circuit breakers clearly indicate whether they are open (off) or closed (on).
    • Install circuit breakers that operate vertically so the handle is in the "up" position when the breaker is closed (on).
    – Circuit breakers used as switches in 120-volt, fluorescent lighting circuits must be approved for that purpose and marked "SWD."
    [Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060, and chapter 49.17 RCW. WSR 12-16-064, § 296-800-28045, filed 7/31/12, effective 9/1/12. Statutory Authority: RCW 49.17.010, [49.17].040, and [49.17].050. WSR 02-16-047, § 296-800-28045, filed 8/1/02, effective 10/1/02; WSR 01-11-038, § 296-800-28045, filed 5/9/01, effective 9/1/01.]
RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060, and chapter 49.17 RCW. WSR 12-16-064, § 296-800-28045, filed 7/31/12, effective 9/1/12. Statutory Authority: RCW 49.17.010, [49.17].040, and [49.17].050. WSR 02-16-047, § 296-800-28045, filed 8/1/02, effective 10/1/02; WSR 01-11-038, § 296-800-28045, filed 5/9/01, effective 9/1/01.