Section 296-59-075. Electrical equipment and distribution.  


Latest version.
  • (1) National Electrical Code to prevail. All electrical installations and electrical utilization equipment shall comply with the National Electrical Code requirements.
    Exception:
    In instances where (N.E.C.) conflicts with ANSI B77.1 with respect to tramways, surface lifts, or tows, ANSI B77.1 shall prevail.
    (2) Authorized personnel to do electrical work. Only those persons who are qualified to do the work assigned and are authorized by the employer shall be allowed to perform electrical work on any electrical equipment or wiring installations.
    (3) High voltage areas to be guarded. Motor rooms, switch panel rooms, or other areas where persons may come in contact with high voltages shall be fenced off or be enclosed in a separate area. The gate, door, or access to such area shall be posted with a notice stating that only authorized persons are allowed in the area.
    (4) Control panels. In areas where mobile equipment operates, floor stand panels shall be protected from being struck by moving equipment. Start or run handles and buttons shall be protected from accidental actuation.
    (5) Switches or control devices. Switches, circuit breakers, or other control devices shall be so located that they are readily accessible for activation or deactivation and shall be marked to indicate their function or machine which they control. The positions of ON and OFF shall be marked or indicated and provision shall be made for locking out the circuit.
    (6) Starting requirements for electrically driven equipment after power failure. Electrically driven equipment shall be so designed that it will not automatically start upon restoration of power after a power failure if it will create a hazard to personnel.
    (7) Posting equipment automatically activated or remotely controlled. Equipment which is automatically activated or remotely controlled shall be posted, warning persons that machine may start automatically if it will create a hazard to personnel.
    [Statutory Authority: Chapter 49.17 RCW. WSR 88-14-108 (Order 88-11), § 296-59-075, filed 7/6/88.]