Section 296-52-67065. Vibration and damage control.  


Latest version.
  • (1) Ground vibration - maximum limits.
    Either Table 8-A or Table 8-B can be used to determine the maximum limits of ground vibration for any dwelling, public building, school church, commercial site, cofferdams, piers, underwater structures, or institutional building nearby the blasting site. The methods used for monitoring vibration and calculating frequency must be included in the blast plan.
    (a) Frequency versus particle velocity graphics. In lieu of Table 8-A, a blasting operation has the option to use the graphs shown in Figure 8a or 8b to limit peak particle velocity based upon the frequency of the blast vibration. If either of the graphs in Figure 8a or 8b is used to limit vibration levels, the methods used for monitoring vibration and calculating frequency must be included in the blast plan.
    Figure 8a
    Alternative Blasting Level Criteria
    Figure 8b
    Alternative Blasting Level Criteria
    (b) Scaled distance equations. Unless a blasting operation uses a seismograph to monitor a blast to assure compliance with Table 8-A or Figures 9a or 8b, the operation must comply with the scaled distance equations shown in Table 8-B.
    Table 8-B
    SCALED-DISTANCE EQUATIONS
    Note:
    To convert English Units of scaled distances (ft/lb2) to metric units (m/kg2) divide by a factor of 2.21.
    (2) Air blast - Maximum limits. Air blast must not exceed the maximum limits listed in Table 8-C. Use Table 8-C to determine maximum air blast limits at any dwelling, public building, school, church, commercial, or institutional building not owned, leased, contracted, or on the property where the owner has not provided a written waiver to the blasting operation.
    Table 8-C
    AIR-BLAST LIMITS
    (3) Flyrock outside the blast area:
    (a) Uncontrolled flyrock. Flyrock traveling in the air or along the ground cannot be cast from the blast area in an uncontrolled manner, which could result in personal injury or property damage. Uncontrolled flyrock (airborne or along the ground), that could cause personal injury or property damage, is not allowed from the blast area.
    (b) Contract or written waiver. Flyrock cannot be propelled from the blast area onto property where the blasting operation has not contracted or received a written waiver from the owner.
    (c) Use of protective material. When blasting in congested areas or close to a structure, railway, highway, or any other installation that could be damaged, the blast must be covered, before firing, with a mat or other protective material that will prevent fragments from being thrown.
    [Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 03-06-073, § 296-52-67065, filed 3/4/03, effective 8/1/03. Statutory Authority: RCW 49.17.010, [49.17].040, and [49.17].050. WSR 02-03-125, § 296-52-67065, filed 1/23/02, effective 3/1/02.]