Section 296-307-48027. What requirements apply to low pressure oxygen manifolds?  


Latest version.
  • This section applies to cylinders with a maximum DOT service pressure of 200 psig.
    (1) Manifolds must be of substantial construction suitable for use with oxygen at a pressure of 250 psig. They must have a minimum bursting pressure of 1,000 psig and must be protected by a safety-relief device that will relieve at a maximum pressure of 500 psig.
    Note:
    DOT-4L200 cylinders have safety devices that relieve at a maximum pressure of 250 psig (or 235 psig if vacuum insulation is used).
    (2) Hose and hose connections subject to cylinder pressure must meet the requirements of WAC 296-307-48049. Hose must have a minimum bursting pressure of 1,000 psig.
    (3) The assembled manifold including leads must be tested and proven gas-tight at a pressure of 300 psig. The fluid used for testing oxygen manifolds must be oil-free and not combustible.
    (4) The location of manifolds must meet the requirements of WAC 296-307-48025.
    (5) The following sign must be conspicuously posted at each manifold:
    Low-Pressure Manifold
    Do Not Connect High-Pressure Cylinders
    Maximum Pressure—250 PSIG
    [Statutory Authority: RCW 49.17.040. WSR 98-24-096, § 296-307-48027, filed 12/1/98, effective 3/1/99. WSR 97-09-013, recodified as § 296-307-48027, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040, [49.17.]050 and [49.17.]060. WSR 96-22-048, § 296-306A-48027, filed 10/31/96, effective 12/1/96.]