Section 296-307-45515. Provide bottom drains.  


Latest version.
  • Exemption:
    A bottom drain is not required if:
     
    – The viscosity of the liquid makes it impractical to empty the tank by gravity or pumping
     
    OR
     
    – The dip tank has an automatic closing cover that meets the requirements of WAC 296-307-45530.
    You must:
    • Provide a bottom drain on all dip tanks that hold more than five hundred gallons of liquid
    • Make sure the bottom drain:
    – Is properly trapped
    – Will empty the dip tank during a fire
    – Has pipes large enough to empty the tank within five minutes
    – Uses automatic pumps if gravity draining is not practical
    – Is capable of both manual and automatic operation
    – Discharges to a safe location.
    Note:
    Discharges to a safe location could be a:
     
    • Safe location outside the building
     
    OR
     
    • Closed, properly vented salvage tank or tanks that can hold more than the dip tank.
    You must:
    • Make sure manual operation of the bottom drain is performed from a safe and easily accessible location.
    [Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 03-10-068, § 296-307-45515, filed 5/6/03, effective 8/1/03.]