Section 296-307-45015. Take additional precautions if you recirculate ventilation system exhaust air into the workplace.  


Latest version.
  • You must:
    • Only recirculate air that contains no substance at a concentration that could pose a health or safety hazard to employees
    • Make sure any exhaust system that recirculates air into the workplace:
    – Passes the air through a device that removes contaminants
    – Sounds an alarm and automatically shuts down the dip tank operation, if the vapor concentration of any substance in the exhaust air exceeds twenty-five percent of its LFL
    – Monitors the concentration of vapor from flammable or combustible liquids with approved equipment.
    Note:
    • The LFL concentration in the air must be determined after the air passes through the air-cleaning device and before the air reenters the workspace
     
    • Most substances will pose a health hazard at a concentration far below twenty-five percent of its LFL.
    [Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 03-10-068, § 296-307-45015, filed 5/6/03, effective 8/1/03; WSR 97-09-013, recodified as § 296-307-45015, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040, [49.17.]050 and [49.17.]060. WSR 96-22-048, § 296-306A-45015, filed 10/31/96, effective 12/1/96.]
RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 03-10-068, § 296-307-45015, filed 5/6/03, effective 8/1/03; WSR 97-09-013, recodified as § 296-307-45015, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040, [49.17.]050 and [49.17.]060. WSR 96-22-048, § 296-306A-45015, filed 10/31/96, effective 12/1/96.