Section 296-307-34512. How must employee alarm systems be maintained and tested?  


Latest version.
  • (1) You must ensure that all employee alarm systems are maintained in operating condition except when undergoing repairs or maintenance.
    (2) You must ensure that a test of the reliability and adequacy of nonsupervised employee alarm systems is made every two months. You must use a different actuation device in each test of a multiactuation device system so that no individual device is used for two consecutive tests.
    (3) You must maintain or replace power supplies as often as necessary to ensure fully operational condition. You must provide back-up alarms, such as employee runners or telephones, when systems are out of service.
    (4) You must ensure that supervised employee alarm circuitry is supervised and that it will provide positive notification to assigned personnel whenever a deficiency exists in the system. You must ensure that all supervised employee alarm systems are tested at least annually for reliability and adequacy.
    (5) You must ensure that employee alarms are serviced, maintained, and tested by someone trained in the operation and functions necessary for reliable and safe operation of the system.
    [WSR 97-09-013, recodified as § 296-307-34512, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040, [49.17.]050 and [49.17.]060. WSR 96-22-048, § 296-306A-34512, filed 10/31/96, effective 12/1/96.]
WSR 97-09-013, recodified as § 296-307-34512, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040, [49.17.]050 and [49.17.]060. WSR 96-22-048, § 296-306A-34512, filed 10/31/96, effective 12/1/96.