Section 296-304-06005. Utilities.  


Latest version.
  • (1) Steam supply and hoses.
    (a) Prior to supplying a vessel with steam from a source outside the vessel, the employer shall ascertain from responsible vessel's representatives, having knowledge of the condition of the plant, the safe working pressure of the vessel's steam system. The employer shall install a pressure gauge and a relief valve of proper size and capacity at the point where the temporary steam hose joins the vessel's steam piping system or systems. The relief valve shall be set and capable of relieving at a pressure not exceeding the safe working pressure of the vessel's system in its present condition, and there shall be no means of isolating the relief valve from the system which it protects. The pressure gauge and relief valve shall be located so as to be visible and readily accessible, and each relief valve is to be positioned so it is not likely to cause injury if steam is released.
    (b) Steam hose and fittings shall have a safety factor of not less than five, and shall be used in accordance with the manufacturer's specifications.
    (c) When steam hose is hung in a bight or bights, the weight shall be relieved by appropriate lines to reduce tension on the hose and its fittings. The hose shall be protected against chafing.
    (d) Steam hose shall be protected from damage and hose and temporary piping shall be so shielded where passing through normal work areas as to prevent accidental contact by employees.
    (2) Electric power. When the vessel is supplied with electric power from a source outside the vessel, the following precautions shall be taken prior to energizing the vessel's circuits:
    (a) If in dry dock, the vessel shall be adequately grounded.
    (b) The employer shall ascertain from responsible vessel's representatives, having a knowledge of the condition of the vessel's electrical system, that all circuits to be energized are in a safe condition.
    (c) All circuits to be energized shall be equipped with overcurrent protection of capacity not exceeding the rated current carrying capacity of the cord used.
    (3) Infrared electrical heat lamps. All infrared electrical heat lamps shall be equipped with guards that surround the lamps with the exception of the face, to minimize accidental contact with the lamps.
    [Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060, and chapter 49.17 RCW. WSR 12-12-060, § 296-304-06005, filed 6/5/12, effective 8/1/12; Order 74-25, § 296-304-06005, filed 5/7/74.]