Section 246-359-170. Wood framed construction and concrete masonry unit (CMU) general limitations.  


Latest version.
  • (1) When building with wood or CMU as required by WAC 246-359-200 through 246-359-580 the following requirements apply:
    (a) Floor area must be limited to three thousand six hundred square feet per building;
    (b) Height must be limited to one story; and
    (c) All floor surfaces must be above grade, no basements.
    (2) When building to WAC 246-359-600, alternate construction, the limitations in subsection (1) of this section do not apply.
    [Statutory Authority: RCW 70.114A.081. WSR 99-03-065, § 246-359-170, filed 1/18/99, effective 2/18/99.]
RCW 70.114A.081. WSR 99-03-065, § 246-359-170, filed 1/18/99, effective 2/18/99.