Chapter 173-360. Underground storage tank regulations. |
Section 173-360-750. Emergency response requirements.
Latest version.
- (1) Presence of operators. While an UST facility is manned, UST system owners and operators shall ensure at least one of the individuals manning the facility is a properly trained Class A, Class B, or Class C operator.(2) Signage. At each UST facility, UST system owners and operators shall post and maintain signage providing emergency response information. The signage must:(a) Be posted in prominent areas of the facility that are easily visible to individuals who dispense or deliver regulated substances;(b) Identify the location of fire extinguishers and any emergency shut-off devices at the facility; and(c) Provide instructions on what to do in case of an emergency at the facility. At a minimum, the instructions must include the following or equivalent wording:(Name and address of facility)IN CASE OF FIRE, SPILL OR RELEASE(Insert if applicable: Use emergency shut off)Call the fire department: (911 or local fire department telephone number)Call the facility operator: (24-hour telephone number)[Statutory Authority: Chapter 90.76 RCW. WSR 12-17-041 (Order 08-08), § 173-360-750, filed 8/8/12, effective 10/1/12.]
Chapter 90.76 RCW. WSR 12-17-041 (Order 08-08), § 173-360-750, filed 8/8/12, effective 10/1/12.